Product Details
Place of Origin: Austria
Brand Name: B&R
Model Number: X20BC0073
Payment & Shipping Terms
Product Family: |
X20 System |
Controller Type: |
CAN I/O Bus Controller |
Fieldbus Role: |
CAN I/O Slave |
Connector: |
5-pin Male Multipoint Connector |
Maximum Transfer Rate: |
1 Mbit/s |
Maximum Network Distance: |
1000 M |
X2X Link Cycle: |
Fixed At 1 Ms |
Terminating Resistor: |
Integrated |
Maximum Logic I/O Modules: |
43 |
Maximum Analog Modules: |
16 Within The 43-module Total |
Electrical Isolation: |
CAN I/O Isolated From I/O |
Bus Power Consumption: |
1.5 W |
Operating Temperature: |
-25 To 60°C Horizontal; -25 To 50°C Vertical |
Protection Rating: |
IP20 |
Module Pitch: |
37.5 Mm |
Required Components: |
X20BB80, X20PS9400 Or X20PS9402, X20TB12 And TB2105 |
Product Family: |
X20 System |
Controller Type: |
CAN I/O Bus Controller |
Fieldbus Role: |
CAN I/O Slave |
Connector: |
5-pin Male Multipoint Connector |
Maximum Transfer Rate: |
1 Mbit/s |
Maximum Network Distance: |
1000 M |
X2X Link Cycle: |
Fixed At 1 Ms |
Terminating Resistor: |
Integrated |
Maximum Logic I/O Modules: |
43 |
Maximum Analog Modules: |
16 Within The 43-module Total |
Electrical Isolation: |
CAN I/O Isolated From I/O |
Bus Power Consumption: |
1.5 W |
Operating Temperature: |
-25 To 60°C Horizontal; -25 To 50°C Vertical |
Protection Rating: |
IP20 |
Module Pitch: |
37.5 Mm |
Required Components: |
X20BB80, X20PS9400 Or X20PS9402, X20TB12 And TB2105 |
The B&R X20BC0073 connects X2X Link I/O nodes to a CAN I/O network. The controller supports automatic firmware updates through the fieldbus, integrated Automation Studio access and a fixed 1 ms X2X Link cycle.
This model differs from the CANopen-based X20BC0043-10. X20BC0073 uses B&R CAN I/O and is intended for compatible B&R system architectures. It supports up to 43 logic I/O modules, including a maximum of 16 analog modules.
Key Features
Typical Applications
FAQ
Q: Is CAN I/O the same as CANopen?
A: No. Both use CAN physical communication, but CAN I/O and CANopen are different higher-level protocols.
Q: How many modules can be connected?
A: Up to 43 logic I/O modules can be connected, with no more than 16 analog modules within that total.
Q: Does the controller include a CAN connector?
A: A compatible five-pin TB2105 terminal must be ordered separately.
Tags: