Product Details
Place of Origin: Austria
Brand Name: B&R
Model Number: X20BC0043-10
Payment & Shipping Terms
Product Family: |
X20 System |
Controller Type: |
CANopen Bus Controller |
Fieldbus Role: |
CANopen Slave |
Connector: |
5-pin Male Multipoint Connector |
Maximum Transfer Rate: |
1 Mbit/s |
Maximum Network Distance: |
1000 M |
X2X Link Cycle: |
500 µs |
Configurable I/O Cycle: |
0.5 To 4 Ms |
CAN Terminating Resistor: |
Integrated |
Maximum PDO Capacity: |
32 Receive And 32 Transmit PDOs |
Electrical Isolation: |
CANopen Isolated From I/O |
Bus Power Consumption: |
1.5 W From Revision H0 |
Operating Temperature: |
-25 To 60°C Horizontal; -25 To 50°C Vertical |
Protection Rating: |
IP20 |
Module Pitch: |
37.5 Mm |
Required System Components: |
X20BB80, X20PS9400 Or X20PS9402 And X20TB12 |
Fieldbus Terminal: |
TB2105 Ordered Separately |
Product Family: |
X20 System |
Controller Type: |
CANopen Bus Controller |
Fieldbus Role: |
CANopen Slave |
Connector: |
5-pin Male Multipoint Connector |
Maximum Transfer Rate: |
1 Mbit/s |
Maximum Network Distance: |
1000 M |
X2X Link Cycle: |
500 µs |
Configurable I/O Cycle: |
0.5 To 4 Ms |
CAN Terminating Resistor: |
Integrated |
Maximum PDO Capacity: |
32 Receive And 32 Transmit PDOs |
Electrical Isolation: |
CANopen Isolated From I/O |
Bus Power Consumption: |
1.5 W From Revision H0 |
Operating Temperature: |
-25 To 60°C Horizontal; -25 To 50°C Vertical |
Protection Rating: |
IP20 |
Module Pitch: |
37.5 Mm |
Required System Components: |
X20BB80, X20PS9400 Or X20PS9402 And X20TB12 |
Fieldbus Terminal: |
TB2105 Ordered Separately |
The B&R X20BC0043-10 connects X20 and other X2X Link I/O nodes to a CANopen network as a slave device. It supports automatic transfer-rate detection, an integrated terminating resistor, heartbeat functions, emergency messaging and configurable I/O cycles.
Unlike the X20BC0073, which uses B&R CAN I/O, the X20BC0043-10 implements the standardized CANopen protocol. It is therefore the appropriate choice when an external CANopen master must exchange cyclic PDO data with an X20 I/O station.
Key Features
Typical Applications
FAQ
Q: Is X20BC0043-10 a CANopen master?
A: No. It operates as a CANopen slave and requires a compatible CANopen master.
Q: How does it differ from X20BC0073?
A: X20BC0043-10 uses the standardized CANopen protocol. X20BC0073 uses B&R CAN I/O and is intended for integration within compatible B&R control systems.
Q: Which accessories are required?
A: The controller requires X20BB80, X20PS9400 or X20PS9402, X20TB12 and a compatible five-pin TB2105 fieldbus terminal.
Tags: