Product Details
Place of Origin: Austria
Brand Name: B&R
Model Number: X20SO4110
Payment & Shipping Terms
Product Family: |
X20 SafeIO |
Module Type: |
Four-channel Safe Semiconductor Output Module |
Safety Application: |
Up To Cat. 4 / PL E And SIL 3 In A Validated System |
Safe Outputs: |
4 Type A Digital Outputs |
Output Circuit: |
FET; Positive And Negative Switching Paths |
Nominal Voltage: |
24 VDC |
Nominal Output Current: |
0.5 A Per Channel; 2 A Total |
Current Monitoring: |
Yes, Including Open-circuit Detection |
OSSD Test Pulse: |
Less Than 500 µs |
Internal I/O Power: |
1.3 W |
Electrical Isolation: |
Channels Isolated From Bus |
Operating Temperature: |
0 To 60°C Horizontal; 0 To 50°C Vertical |
Protection Rating: |
IP20 |
Module Pitch: |
25 Mm |
Required Bus Module: |
X20BM33 Or X20BM36 |
Required Terminal Block: |
1 × X20TB52 Safety-keyed Terminal Block |
Product Family: |
X20 SafeIO |
Module Type: |
Four-channel Safe Semiconductor Output Module |
Safety Application: |
Up To Cat. 4 / PL E And SIL 3 In A Validated System |
Safe Outputs: |
4 Type A Digital Outputs |
Output Circuit: |
FET; Positive And Negative Switching Paths |
Nominal Voltage: |
24 VDC |
Nominal Output Current: |
0.5 A Per Channel; 2 A Total |
Current Monitoring: |
Yes, Including Open-circuit Detection |
OSSD Test Pulse: |
Less Than 500 µs |
Internal I/O Power: |
1.3 W |
Electrical Isolation: |
Channels Isolated From Bus |
Operating Temperature: |
0 To 60°C Horizontal; 0 To 50°C Vertical |
Protection Rating: |
IP20 |
Module Pitch: |
25 Mm |
Required Bus Module: |
X20BM33 Or X20BM36 |
Required Terminal Block: |
1 × X20TB52 Safety-keyed Terminal Block |
The B&R X20SO4110 expands the 0.5 A type A safe output architecture to four channels. It is designed for floating 24 VDC actuators that require positive and negative switching, current monitoring and open-circuit diagnostics.
Compared with X20SO2110, it doubles the channel count from two to four while retaining the 0.5 A per-channel rating. Compared with X20SO4120, it is intended for lower-current loads and has a 2 A total nominal current rather than the 5 A total capacity of the 2 A-per-channel model.
The four-channel format is useful when several safety contactors, relays or valves must be controlled from one SafeIO station without moving to a higher-current output design.
The X20SO4110 can be used in safety-related applications up to PL e or SIL 3 only when the complete safety function is correctly engineered, configured, commissioned and validated. The achievable safety level depends on the full sensor, logic, communication, wiring and actuator chain. Check the exact hardware revision, firmware, Automation Studio hardware definition and SafeDESIGNER project before replacing an installed module.
Q: How does X20SO4110 differ from X20SO2110?
A: X20SO4110 has four 0.5 A outputs, while X20SO2110 has two.
Q: How does it differ from X20SO4120?
A: Both have four type A outputs, but X20SO4110 is rated at 0.5 A per channel and X20SO4120 at 2 A per channel.
Q: What is the total nominal current?
A: The total nominal output current is 2 A.
Q: Does it provide load diagnostics?
A: Yes. Current monitoring supports open-circuit detection.
Q: Which actuator type suits a type A output?
A: Type A outputs are intended for floating loads such as suitable relays, contactors and valves.
Q: Must the safety function be retested after replacement?
A: Yes. Wiring, load behavior, firmware and the complete validated safety function must be checked.
Tags: