Product Details
Place of Origin: Austria
Brand Name: B&R
Model Number: X20BC0088
Payment & Shipping Terms
Product Family: |
X20 System |
Controller Type: |
Industrial Ethernet Bus Controller |
Fieldbus Role: |
EtherNet/IP Adapter |
Ethernet Interface: |
2 Shielded RJ45 Ports With Integrated Switch |
Physical Layer: |
10BASE-T And 100BASE-TX |
Transfer Rate: |
10/100 Mbit/s |
Minimum Fieldbus Cycle: |
1 Ms |
X2X Link Cycle: |
500 µs |
Configurable I/O Cycle: |
0.5 To 4 Ms |
Network Configuration: |
DHCP Supported |
Web Interface: |
Integrated |
Electrical Isolation: |
Fieldbus Isolated From Bus And I/O |
Bus Power Consumption: |
2 W |
Operating Temperature: |
-25 To 60°C Horizontal; -25 To 50°C Vertical |
Protection Rating: |
IP20 |
Module Pitch: |
37.5 Mm |
Required Components: |
X20BB80, X20PS9400 Or X20PS9402 And X20TB12 |
Product Family: |
X20 System |
Controller Type: |
Industrial Ethernet Bus Controller |
Fieldbus Role: |
EtherNet/IP Adapter |
Ethernet Interface: |
2 Shielded RJ45 Ports With Integrated Switch |
Physical Layer: |
10BASE-T And 100BASE-TX |
Transfer Rate: |
10/100 Mbit/s |
Minimum Fieldbus Cycle: |
1 Ms |
X2X Link Cycle: |
500 µs |
Configurable I/O Cycle: |
0.5 To 4 Ms |
Network Configuration: |
DHCP Supported |
Web Interface: |
Integrated |
Electrical Isolation: |
Fieldbus Isolated From Bus And I/O |
Bus Power Consumption: |
2 W |
Operating Temperature: |
-25 To 60°C Horizontal; -25 To 50°C Vertical |
Protection Rating: |
IP20 |
Module Pitch: |
37.5 Mm |
Required Components: |
X20BB80, X20PS9400 Or X20PS9402 And X20TB12 |
The B&R X20BC0088 integrates X20 I/O stations into an EtherNet/IP network as an adapter device. It combines dual external RJ45 connections, an integrated switch, DHCP support and a web interface for configuration and diagnostics.
Unlike X20BC0087, which communicates through Modbus TCP or UDP, X20BC0088 exchanges cyclic I/O data through EtherNet/IP. Its 1 ms minimum fieldbus cycle makes it suitable for fast distributed machine I/O, while advanced multifunction-module configurations can be transferred through the configuration assembly.
Key Features
Typical Applications
FAQ
Q: Does X20BC0088 operate as an EtherNet/IP scanner?
A: No. It operates as an adapter and requires a scanner or master on the network.
Q: What is the difference from X20BC0087?
A: X20BC0088 uses EtherNet/IP, while X20BC0087 supports Modbus TCP and Modbus UDP.
Q: Can modules be configured through the network?
A: Yes. Automatic I/O configuration is supported, and additional configuration data can be transferred using a configuration assembly.
Tags: