Product Details
Place of Origin: Austria
Brand Name: B&R
Model Number: X20AI4622
Payment & Shipping Terms
Minimum Order Quantity: 1 piece
Packaging Details: Carton packaging
Delivery Time: 3-7 working days
Payment Terms: D/A, D/P, T/T, Western Union
Product Family: |
X20 System |
Module Type: |
Analog Input Module |
Number Of Inputs: |
4 |
Supported Voltage Signal: |
±10 V |
Supported Current Signals: |
0 To 20 MA And 4 To 20 MA |
Input Type: |
Differential |
Converter Resolution: |
13-bit Including Sign |
Conversion Time: |
400 µs For All Inputs |
Voltage Input Impedance: |
20 MΩ |
Current Input Load: |
Less Than 400 Ω |
Conversion Method: |
SAR |
Input Filter: |
Third-order Low-pass, 1 KHz Cutoff |
Electrical Isolation: |
Channels Isolated From Bus |
Power Consumption: |
0.01 W Bus; 1.1 W Internal I/O |
Required Terminal Block: |
X20TB12, Ordered Separately |
Compatible Bus Module: |
X20BM11 Or X20BM15, Ordered Separately |
Operating Temperature: |
-25 To 60°C Horizontal; -25 To 50°C Vertical |
Protection Rating: |
IP20 |
Product Family: |
X20 System |
Module Type: |
Analog Input Module |
Number Of Inputs: |
4 |
Supported Voltage Signal: |
±10 V |
Supported Current Signals: |
0 To 20 MA And 4 To 20 MA |
Input Type: |
Differential |
Converter Resolution: |
13-bit Including Sign |
Conversion Time: |
400 µs For All Inputs |
Voltage Input Impedance: |
20 MΩ |
Current Input Load: |
Less Than 400 Ω |
Conversion Method: |
SAR |
Input Filter: |
Third-order Low-pass, 1 KHz Cutoff |
Electrical Isolation: |
Channels Isolated From Bus |
Power Consumption: |
0.01 W Bus; 1.1 W Internal I/O |
Required Terminal Block: |
X20TB12, Ordered Separately |
Compatible Bus Module: |
X20BM11 Or X20BM15, Ordered Separately |
Operating Temperature: |
-25 To 60°C Horizontal; -25 To 50°C Vertical |
Protection Rating: |
IP20 |
The B&R X20AI4622 is a flexible four-channel analog input module for mixed voltage and current signals. Each channel can acquire ±10 V, 0 to 20 mA or 4 to 20 mA signals through the corresponding terminal connections.
This module emphasizes signal flexibility and native 4 to 20 mA configuration. Compared with X20AI4632, it has lower converter resolution and a longer conversion time, but supports the dedicated 4 to 20 mA measuring range frequently used by industrial transmitters.
Key Features
Typical Applications
FAQ
Q: Can voltage and current signals be used on the same module?
A: Yes. Signal type is selected through the corresponding terminal connections and project configuration.
Q: What is the main difference from X20AI4632?
A: X20AI4622 provides 13-bit resolution, a 400 µs conversion time and native 4 to 20 mA support. X20AI4632 provides higher resolution and faster conversion.
Q: Are channels individually isolated?
A: The channels are isolated from the bus but are not galvanically isolated from one another.
Tags: