Product Details
Place of Origin: Austria
Brand Name: B&R
Model Number: X20AT6402
Payment & Shipping Terms
Product Family: |
X20 System |
Module Type: |
Thermocouple Temperature Input Module |
Number Of Inputs: |
6 |
Supported Thermocouples: |
J, K, N, S, B And R |
Type J Range: |
-210 To 1200°C |
Type K Range: |
-270 To 1372°C |
Type N Range: |
-270 To 1300°C From Revision D0 |
Type S Range: |
-50 To 1768°C |
Type B Range: |
0 To 1820°C |
Type R Range: |
-50 To 1664°C |
Temperature Resolution: |
0.1°C Or 0.01°C |
Converter Resolution: |
16-bit |
Filter Time: |
1 To 66.7 Ms, Configurable |
Terminal Compensation: |
Integrated |
Conversion Method: |
Sigma-delta |
Electrical Isolation: |
Channels Isolated From Bus |
Power Consumption: |
0.01 W Bus; 0.91 W Internal I/O |
Required Terminal Block: |
X20TB12, Ordered Separately |
Operating Temperature: |
0 To 55°C Horizontal; 0 To 50°C Vertical |
Protection Rating: |
IP20 |
Product Family: |
X20 System |
Module Type: |
Thermocouple Temperature Input Module |
Number Of Inputs: |
6 |
Supported Thermocouples: |
J, K, N, S, B And R |
Type J Range: |
-210 To 1200°C |
Type K Range: |
-270 To 1372°C |
Type N Range: |
-270 To 1300°C From Revision D0 |
Type S Range: |
-50 To 1768°C |
Type B Range: |
0 To 1820°C |
Type R Range: |
-50 To 1664°C |
Temperature Resolution: |
0.1°C Or 0.01°C |
Converter Resolution: |
16-bit |
Filter Time: |
1 To 66.7 Ms, Configurable |
Terminal Compensation: |
Integrated |
Conversion Method: |
Sigma-delta |
Electrical Isolation: |
Channels Isolated From Bus |
Power Consumption: |
0.01 W Bus; 0.91 W Internal I/O |
Required Terminal Block: |
X20TB12, Ordered Separately |
Operating Temperature: |
0 To 55°C Horizontal; 0 To 50°C Vertical |
Protection Rating: |
IP20 |
The B&R X20AT6402 acquires six thermocouple signals and performs internal temperature linearization and terminal compensation. It supports types J, K, N, S, B and R, covering both standard machine heating zones and high-temperature furnace applications.
The module can output normalized temperature values at 0.1°C or 0.01°C resolution and can also provide direct raw millivolt measurements. Unlike X20AT4222, it is specifically designed for thermocouples rather than Pt100 or Pt1000 resistance sensors.
Key Features
Typical Applications
FAQ
Q: Does X20AT6402 support Type T or Type E thermocouples?
A: No. The specified sensor types are J, K, N, S, B and R.
Q: Is an external cold-junction compensation sensor required?
A: The module includes internal terminal temperature compensation.
Q: Can X20AT6402 replace X20AT4222?
A: No. X20AT6402 accepts thermocouples, while X20AT4222 is designed for Pt100 and Pt1000 RTD sensors.