Product Details
Place of Origin: Austria
Brand Name: B&R
Model Number: X20BC1083
Payment & Shipping Terms
Product Family: |
X20 System |
Controller Type: |
Expandable POWERLINK Bus Controller |
Fieldbus Role: |
POWERLINK V1/V2 Controlled Node |
POWERLINK Type: |
Type 2 |
Ethernet Interface: |
2 Shielded RJ45 Ports With Integrated Hub |
Physical Layer: |
100BASE-TX |
Transfer Rate: |
100 Mbit/s |
Minimum Fieldbus Cycle: |
200 µs |
X2X Link Cycle: |
200 µs |
Maximum Input Data: |
1488 Bytes |
Maximum Output Data: |
1488 Bytes |
Dynamic Node Allocation: |
Supported |
Synchronization Between Buses: |
Supported |
Interface Expansion Slots: |
Up To 2 |
Electrical Isolation: |
POWERLINK Isolated From Bus And I/O |
Bus Power Consumption: |
2 W |
Operating Temperature: |
-25 To 60°C Horizontal; -25 To 50°C Vertical |
Protection Rating: |
IP20 |
Required Components: |
X20BB81 Or X20BB82, X20PS9400 Or X20PS9402 And X20TB12 |
Product Family: |
X20 System |
Controller Type: |
Expandable POWERLINK Bus Controller |
Fieldbus Role: |
POWERLINK V1/V2 Controlled Node |
POWERLINK Type: |
Type 2 |
Ethernet Interface: |
2 Shielded RJ45 Ports With Integrated Hub |
Physical Layer: |
100BASE-TX |
Transfer Rate: |
100 Mbit/s |
Minimum Fieldbus Cycle: |
200 µs |
X2X Link Cycle: |
200 µs |
Maximum Input Data: |
1488 Bytes |
Maximum Output Data: |
1488 Bytes |
Dynamic Node Allocation: |
Supported |
Synchronization Between Buses: |
Supported |
Interface Expansion Slots: |
Up To 2 |
Electrical Isolation: |
POWERLINK Isolated From Bus And I/O |
Bus Power Consumption: |
2 W |
Operating Temperature: |
-25 To 60°C Horizontal; -25 To 50°C Vertical |
Protection Rating: |
IP20 |
Required Components: |
X20BB81 Or X20BB82, X20PS9400 Or X20PS9402 And X20TB12 |
The B&R X20BC1083 is an expandable POWERLINK controlled node that connects X2X Link I/O stations to a real-time POWERLINK network. It supports 200 µs minimum cycles, synchronized bus operation and up to 1488 bytes of cyclic data in each direction.
Its defining difference from the standard X20BC0083 is expansion capacity. When combined with an X20BB81 or X20BB82 bus base, the X20BC1083 supports one or two additional X20 interface modules for integrating other industrial networks or communication channels.
Key Features
Typical Applications
FAQ
Q: What is the difference between X20BC1083 and X20BC0083?
A: X20BC1083 supports up to two additional X20 interface modules. X20BC0083 uses a standard non-expandable bus-controller base.
Q: Which bus base should be selected?
A: X20BB81 provides one expansion slot, while X20BB82 provides two expansion slots.
Q: Can X20BC1083 operate as a POWERLINK managing node?
A: It is specified as a POWERLINK V1/V2 controlled node. The network requires a compatible managing node.